Resumen
Electric power supply in urban and rural Peru is loaded with issues, especially in the quality of service offered at distribution substations. Voltage fluctuations compromise power quality, leading to equipment breakdowns and inadequate
service delivery. This research tackles the problem of power quality optimization based on the analysis of accurate data and corrective measures using simulation techniques. The effect of setting the transformer tap changer and voltage control device on supply stability was examined using the PandaPower library in Python. Through the strict implementation of the Technical Standard for the Quality of Electric Services (NTCSE) and the Technical Standard for the Quality of Rural Electric Services (NTCSER), the performance of the secondary circuits powered by a transformer of 100 kVA in urban areas and 25kVA in rural areas was evaluated. A threshold of 2.6 V was set to detect borderline cases where corrective actions could be intelligently modified. The findings proved that adjustments of tap changer positions are a viable low-cost option to enhance power quality in networks with small capacity while achieving compliance with the regulations and improving the overall services. This helps improve the power supply quality in rural areas while offering an adaptable approach for power infrastructure optimization in the region. Further studies should aim to fusion real-time monitoring systems and machine learning to improve predictive maintenance and adaptive control strategies, particularly concerning energy policy and sustainable development.
service delivery. This research tackles the problem of power quality optimization based on the analysis of accurate data and corrective measures using simulation techniques. The effect of setting the transformer tap changer and voltage control device on supply stability was examined using the PandaPower library in Python. Through the strict implementation of the Technical Standard for the Quality of Electric Services (NTCSE) and the Technical Standard for the Quality of Rural Electric Services (NTCSER), the performance of the secondary circuits powered by a transformer of 100 kVA in urban areas and 25kVA in rural areas was evaluated. A threshold of 2.6 V was set to detect borderline cases where corrective actions could be intelligently modified. The findings proved that adjustments of tap changer positions are a viable low-cost option to enhance power quality in networks with small capacity while achieving compliance with the regulations and improving the overall services. This helps improve the power supply quality in rural areas while offering an adaptable approach for power infrastructure optimization in the region. Further studies should aim to fusion real-time monitoring systems and machine learning to improve predictive maintenance and adaptive control strategies, particularly concerning energy policy and sustainable development.
| Idioma original | Español (Perú) |
|---|---|
| Páginas (desde-hasta) | 18 |
| - | 26 |
| Publicación | SSRG International Journal of Electrical and Electronics Engineering |
| Volumen | 12 |
| N.º | 2 |
| DOI | |
| Estado | Indizado - 22 feb. 2025 |
Palabras clave
- Quality of electrical
- Voltage variations
- Electrical simulations
- PandaPower
- Simulation
- Electric service
- Singlephase transformer